Project Technical Specification

1.  Shopping Mall

LV Cables

7.24 PVC, PVC/SWA/PVC, PVC/PVC CABLES

Single core PVC, PVC/PVC cables shall comply with SS358, IEC 60227, IEC 60228, IEC 60228A, IEC 60811 and

IEC 60885 with voltage grade of 450/750V.

Multi core cables shall comply with BS6346 with voltage grade of 600/1000V.

High conductivity copper conductors shall comply with IEC 60228, in respect of dimension and resistances.

Where shaped conductors are used, they shall be compacted to reduce dimensions and to give a smoother

profile. Sizes shall be designated by the nominal cross-sectional area.

Where necessary, PVC fillers shall be used between laid-up wires. In the case of cables with extruded bedding,

the cores shall be bound with a non-hygroscopic tape before the bedding is extruded.

For twin and multi-core cables the bedding shall consist of two or more layers of PVC tape. For cables with

circular conductors, the bedding shall be an extruded layer of PVC.

For armoured cables, the armour shall consist of a single layer of galvanised steel wire or tape as specified.

Armouring for single core cables shall consist of non- magnetic material.

The cable shall be finished in an extruded black or grey PVC oversheath, the thickness of which shall comply with

SS358, IEC 60227 as appropriate. The external surface of the oversheath shall be embossed with the voltage

designation and the manufacturer's name.

Corrosion resistant outdoor type cable glands of the appropriate size shall be used where cables enter or exit

from a switchboard/DB and/or where required. Glands shall comply with BS 6121 with integral earth facility. The

termination of armoured cable shall be in accordance to manufacturer's recommendation and/or to the M&E

Engineer's approval.

The sizing of the cable gland shall be based on the nominal dimension of the cable.

Proper compression cable lugs shall be used for terminating the cable cores onto terminals of devices and

equipment.

The cores of the cables shall be identified as follows:

Three Core (three phase) - Brown, Black, Grey

Four Core (three phase) - Brown, Black, Grey, Blue

Auxilliary cable shall be white with black numbers printed on the cores, commencing 1, 2, 3, 4 upwards.

7.25 CROSS-LINKED POLYETHYLENE (XLPE) CABLES

Cross-linked polyethylene (XLPE) cables shall be of 600/1000V grade and shall be stranded copper conductor,

cross-linked polyethylene insulated, PVC inner sheathed with galvanized steel-wire armour (as required) and

PVC over sheathed power cables. All cables shall comply with IEC 60228, IEC 60228A, IEC 60811 and IEC

60885.

The current carrying capacity and the short circuit final temperature of the cable shall comply with IEC 60287 and

IEC 60724 respectively.

Conductors shall be Class 2 annealed compacted stranded plain copper. Insulation shall be cross-linked

polyethylene (XLPE) with a high degree of cross linking, free from contaminants and air voids, good heat

resistance and it shall be applied by an extrusion process. The XLPE insulation shall be suitable for use in wet

and dry locations at conductor temperatures not exceeding 90 deg. C for normal operation, 130 deg. C for

emergency overload condition and 250 deg. C for short circuit conditions (5 seconds max. duration).

The cores shall be identified by using the colours BROWN, BLACK, GREY, BLUE for multi core cables.

Non hygroscopic fillers and bedding may be used as required.

The PVC inner (if required) and outer sheaths shall be by an extrusion process. The outer sheath shall be

treated so as to be termite proof. The armour (if required) shall be of galvanised steel round wires of diameter

2.5mm.

7.26 INSTALLATIONS WITH TWO WIRING COLOURS

Where new circuits wiring the new colour code (Brown, Black, Grey, Blue) are to be added to existing electrical

installations with circuits in the old cable colour code, necessary colour marking and labelling on the cables shall

be made. A warning notice on the two colour codes shall be placed on the relevant distribution boards according

to Local Authority regulations.

7.27 FIRE RESISTANT CABLE

Fire resistant cable shall comply with SS299, IEC 60331, BS6387 category C, W, Z and IEC 60332-3 category A

or B and shall be of voltage grade 600/1000 volts.

The fire resistant cable shall be of multi-stranded copper conductor type with glass mica flame barrier and cross

linked insulation and sheath.

The insulation and sheath material used shall be halogen free with self-extinguishing, flame retardant and low

smoke emission properties.

The glass mica flame barrier used shall be able to maintain the circuit integrity at the rated cable voltage up to

the melting point of the copper conductor.

The insulation and sheath shall be suitable for continuous operation at a temperature of 90°C.

Fire resistant cable shall be strapped or tied to the cable support system as specified in the drawing using

stainless steel cable ties or stainless steel strappings.

The stainless steel material shall be of type 304 or better.

The stainless steel cable ties and strap shall be tested and approved for used in fire resistant wiring systems.

The spacings of the straps/ties shall conform to the manufacturers recommendation but shall in all cases not

exceed 1m interval.

As far as possible, joints in fire resistance cable shall be avoided. Where this is not possible due to extra-long

run, prior written approval from the M&E Engineer shall be obtained. When permitted by the M&E Engineer, the

joint shall be carried out using method and material recommended by the manufacturers.

The joint method and material used shall not undermine the fire, mechanical and electrical integrity of the cable

under all circumstances and are subjected to the M&E Engineer's approval.

All relevant test certificates on the fire resistance cables and support system/accessories shall be submitted to

the M&E Engineer for approval prior to ordering of the cable.

MV Cables

7.5 HIGH VOLTAGE CABLES

7.5.1 General

The work to be carried out includes the supply of all the necessary labour, equipment and materials for the

laying, jointing and termination of all the high voltage cables shown on the tender drawings and as specified

herein. The work shall be carried out to the approval of the power supply company or local power authority

and/or the M&E Engineer.

7.5.2 Type of Cables

XLPE/SWA/PVC Cables

All H.V. cables shall be of XLPE steel wire armoured and PVC overall sheath of the appropriate voltage ratings.

The conductors shall be plain stranded annealed copper. The cables shall be manufactured in accordance to IEC

60502 and/or BS 6622.

The minimum rating of the HV cables shall be as follows:

Nominal Supply Operating Voltage (KV rms,  50Hz)

Minimum Ratings Required

Rated Voltage (KV rms)

Lighting Impulse Withstand Voltage (KV Peak)

5-Minute Power Frequency Withstand Voltage (KV rms)

Rated Short Time Current (KA rms, 3 seconds rating)

15 Minute DC Voltage Test Level (KV)

Maximum Partial Discharge Level at 2.5 Times the Rated Voltage (PC)

11

8.7/15

95

36

25

63

5

The D.C. resistance of the conductors shall comply with IEC 60228.

The current carrying capacity and the short circuit final temperature of the cable shall comply with IEC 60287 and

IEC 60986 respectively.

7.5.3 HV Cable Termination

All HV cable terminations shall be carried out by licensed cable jointer and/or cable jointer approved by the M&E

Engineer using the approved type of heat shrinkable cable termination kits.

The termination shall be carried out strictly in accordance with the manufacturer's installation instructions.

The minimum rating on the HV cable termination kit and the completed terminations shall be as follows:

Nominal Supply Operating Voltage (KV rms,  50Hz)

Minimum Ratings Required

Rated Insulation Voltage (KV rms)

Impulse Withstand Voltage (KV Peak)

1-Minute Power Frequency Withstand Voltage (KV rms)

Maximum Partial Discharge Level at 2.5 Times the Rated Insulation Voltage (PC)

224kg/m3 Salt-Fog Withstand (KV rms)

Minimum All Round Clearance Between Skirts (mm)

Minimum Number of Skirt

11

15

95

36

20

10.9

15

3

Outdoor type termination kit with skirts and non-tracking weather resistant tubing shall be used.

The cable  terminal screws and cable lugs shall be completely sealed/insulated  using propriately sealing

boot/cap upon completion of the termination works.

Cable Route

All H.V. cables shall be laid on cable ladders and/or trays and properly fastened to the ladder and/or tray from

the power supply company’s substation H.V. Switchroom to the Consumer's H.V. Switchroom and from there to

the Transformer Room.

Cable Ducts

All cable ducts entering cable chambers shall be effectively sealed against ingress of water after installation of

cables.

Cable Identification

Each cable in the cable chamber or cable tray shall be identified by a metallic label, with inscription of the

corresponding designation of the switchgear panel, attached to the cable.

Each switchgear panel shall have its position labelled in the cable chamber. The labelling may be in the form of

stencilling by non-removable paint on the beam nearest to the opening of the floor slab.

Cable Installation

All cables shall be laid in full lengths and straight- jointing of cables will not be permitted unless with the

approval of the M&E Engineer. All jointing, cable terminating materials and tools required to complete the cable

installation shall be of the type recommended or manufactured by the cable manufacturer.

Where cables are installed in concrete trough, a 75mm deep bedding of clean sand shall be provided at the

bottom of the trough and another cover of 75mm sand shall be provided after cable lying.

Space factor for installation of cables in ducts or covered concrete troughs shall follow the requirements of the

SSCP5 "Wiring of Electrical Equipment of Buildings".

Pilot and Control Cables

All control cables installed in cable chamber shall be PVC/SWA/PVC, stranded copper conductors of adequate

rating, size and number of cores run on cable trays along the wall.

The pilot and control cables shall terminate in suitable pilot and termination boxes with appropriate cable

glands.

Testing and Commissioning

The subcontractor shall be responsible for the testing of the cables and certifying that they are safe before

energising them.

Tests shall include continuity, phasing out, high pot and insulation resistance. Initial insulation resistance tests

on H.V. cables shall be carried out with a 'motorized' 5kV megger and subsequent pressure testing at high

voltage as directed by the Power Supply Company or local power authority. Two copies of test results shall be

submitted to the M&E Engineer before the cables are energised.

The voltage of the high pot test shall be approximately 75% of the rated power frequency or DC withstands

voltage.

The high pot test shall be carried out with the termination kit installed.